CDWC – Carbon Dioxide Controller
|
||||||
Description
Applications & Features :
- CDWN is suitable for wall mount and CDDN is suitable for duct mount
- High performance NDIR digital sensor and circuit, ensure precise measurement and temperature compensation
- Stable, reliable and fast response
- 15 years sensor life without maintenance
- Digital technology applied, multiple outputs optional, over voltage and reverse polarity protection, high reliability and anti-interference capability
- LCD & function keys can set various parameters, calibrate and adjust output, so the product can be a stand alone controller
Additional information
Sensor | : NDIR sensor, with ABC algorithm (Automatic Baseline Correction) |
---|---|
Sampling Method | : diffusion |
Accuracy | : 50 ppm + 5% reading |
Response time | : <10s (30cc/min, low airflow) |
Drift | <±10ppm/year Range |
Range | : 0~2000 ppm( measure range 400~2000ppm) |
Output | : 2 X SPST, 3A-30VDC/250VAC |
Communication | : optional RS485/Modbus |
Power supply | : 15~28VAC/15-36VDC |
Display and keys | : with LCD Display and 3 touch keys, see more details on LCD & Keys operation |
Display resolution | : 1ppm |
Working environment | : 0~50°C, 0~95%RH(Non-cond.) |
Storage temperature | : -20~80°C |
Housing material | : fireproof ABS |
Protection | : IP30 |
Agency Approval | : CE |
Calibration Protocol | : COML |