ADP14-DM-FLP – Relative Humidity, Dew Point & Temperature
|
||||||
Description
FLAMEPROOF DEWPOINT TEMPERATURE TRANSMITTER
Introduction :
The ADP14-DM-FLP transmitter series incorporate the best high accuracy and great stability relative humidity and dew point
temperature sensors. They convert the measured values into linear 4 to 20 mA signals and optional 0 to 10 Vdc output can also be offered under request
The microprocessor based circuit enables full configuration of output range when used with the PC interface and the Windows based software.
The humidity signal can be configured to either relative humidity or dew point output.
The ADP14-WM-FLP model is dedicated to wall mounted applications and the ADP14-DM-FLP version is suitable for duct and through-the-wall applications in hazardous environments.
Configuration :
ADP14-WM and ADP14-DM configuration is performed by using the software and interface which is connected to a PC RS232 comm port
During configuration the transmitter must be electrically powered and this can be provided by the Config interface which draws power from the RS232 port. Some PC RS232 ports do not provide enough voltage and in this case an external energy source must be used.
A practical choice is to use a 9 V battery attached to the TxConfig interface battery clip. Another way is to energyse the transmitter via its regular loop-power source.
With the configuration one can set the transmitted output range, correct measuring deviations (zero correction) and choose sensor failure conditions (upscale or downscale). Sensor internal information as serial number, product version and model can be also be digitally presented in the programming software menu.
The factory defauld settings are:
- Humidity measuring range: 0 to 100%;
- Temperature measuring range: 0 to 100°C;
- Upscale signal outputs when sensor break or failure.
Additional information
| Humidity Transmitter | — |
|---|---|
| HT - Power | : from 12 Vdc to 30 Vdc (model 4-20 mA) or 18 to 30 Vdc (model 0-10 V). |
| HT - Output resolution | : 0.022 mA (4-20 mA) or 0.015 V (0-10 V). |
| HT - Accuracy | : refer to diagram. |
| HT - Repetibility | : ±1%RH. |
| HT - Histeresis | : ±1%RH. |
| HT - Non-linearity | : <<1%RH. |
| HT - | : <1%RH per year. |
| HT - Range | : programmable anywhere from 0 to 100%RH or from –40 and 100°C for dew point. |
| HT - Response Time | : 4 s in fairly still air |
| Temperature Transmitter | — |
| Power | : from 12 Vdc to 30 Vdc (model 4-20 mA) or 18 to 30 Vdc (model 0-10 V). |
| Output resolution | : 0.006 mA (4-20 mA) or 0.003 V (0-10 V). |
| Accuracy | : refer to diagram. |
| Repetibility | : ±0.1°C. |
| Range | : programmable between -40 and 120°C. |
| Response time | :up to 30s in fairly still air. |