Features : |
 |
Self powered, no external power supplyrequired |
 |
1-5VDC output, connects directly toautomation systems |
 |
One sensor for three ranges, jumper selected |
 |
Low cost, replaces digital status relays |
 |
Panel mounting |
|
 |
Description : |
The CS Current Sensor is a solid state transducer for measuring the current in fans, pumps and other HVAC equipment.Select one of three ranges by moving a jumper onthe device to operate over 10A,
20A and 50A. This sensor outputs 0-5V directly and requires no power supply. Clamping / Split Core Current Transformer is designed
to provide a low cost method to monitoring electrical current.
A unique hinge and locking snap allows attachment without interrupting the current-carrying wire.
High secondary turn will develop signals up to 10Vac across a burden resistor. |
 |
Specifications : |
 |
Power Supply |
: |
Not required |
 |
Operating Temperature |
: |
-20 ~ 60 OC |
 |
Operating Humidity |
: |
0 ~ 95% RH |
 |
CT Material |
: |
ABS (UL94) |
 |
CT Ranges |
: |
10, 20, 50Amp, jumper selected |
 |
Output Signal |
: |
1~5VDC; porportional to average current |
 |
Accuracy |
: |
2% |
 |
Plastic housing |
: |
Flammability rating UL94V0 file E194560 |
|
 |
|
|