FS323 – Flameproof Differential Pressure Transmitter (FLP)
|
||||||
Description
Special Features :
Compact Design with Piezo Resistive Sensor ± 0.25% Accuracy High protection rate up to IP66 with FLP enclosure 4-20 mA or 0-10 VDC Output
Application :
DP Filter Status, Duct Static Pressure, Fan and Blower Pressure, Paint Booths, Dust Collectors, Glove Box Pressure, Bubbler Systems,Cabinet Purging.
Additional information
| Maximum Pressure | : Ranges 5 PSI (35 kPa) =15 PSI (100kPa) Max Ranges > 5PSI (35 kPa)= 30 PSI (200 kPa) Max |
|---|---|
| Media Compatibility | : Air and compatible non combustible, non corrosive gasses |
| Accuracy | : Ranges <4” w.c. (1 kPa) ± 0.5% Ranges >5” w.c. (1.25 kPa) ± 0.25% |
| Temperature Ranges | — |
| Compensated | : ± 0.028% FS/OF (± 0.050%/°C) |
| Operating | : -10° to 155°F (-25° to 70°C) |
| Thermal Effect | : ± 0.028% FS/°F (± 0.050%/°C) |
| Stability | : ± 0.25% FS/year |
| Housing Material | : Diecast Aluminium, Alloy LM6 |
| Output Signal | : 4-20 mA, 2 wire or 0-10VDC, 3 WIRE |
| Loop Resistance | : 250 Ω @ 24 VDC |
| Power Supply | : 12-30 VDC |
| Enclosure Rating | : IP 66 with FLP Enclosure |
| Electrical Connections | : Screw terminals |
| Electricity Entry | : ¾th E.T Cable Gland |
| Process Connections | : Barbed fittings for 3/16” flexible tubing |
| Agency Approval | : CE, CMFRI, CCOE |
| Calibration Protocol | : COML |
| Ex Protection | : Flameproof Ex ‘d’ |
| Zones & Gas Groups | : Gas Groups I, IIA, IIB and Zone 1 & 2 |