AG100: Digital Pressure Gauge
Model : AG100
Temperature : -10 to 70°C
Range : -1 to 350 bar
Battery Life : 4000 hours
Accuracy : ± 0.5% of F.S
Output : NIL

Description :

The AG100 series is a media isolated digital pressure gauge featuring multiple measurement units, min/max readings, selectable tare/zero and an automatic power
off to conserve battery power. Also, a backlight provides improved visibility under marginal lighting conditions.

The AG100 will operate with any liquid or gas that is compatible with 17-4PH stainless steel. Please consult the factory for other available wetted materials.

The design of this one-piece sensing element contains no silicone oil, welds or internal O-rings. The AG100 is ideal for oxygen service, hydrogen* tanks and other critical applications where fluid filled gauges cannot be used.

Specifications :

Display Update Rate : 2 samples per second
Power : 9 Volt Alkaline Battery
Automatic Power Off : 1 Hour
Battery Life : 4000 Hours Operation (typical)
Protection Rating : NEMA 4, IP 65
Instrument Case   Poly carbonate
Performance @ 25°C (77°F) :
Pressure Range : A number of preset ranges are available
Measurement Units : PSI, BAR, kg/cm, ATM, InH20, InHg
Accuracy : <±0.5% BFSL (Includes Non-linearity,
  Hysteresis and Non-repeatability)
Stability (1 year) : ±0.25% FS (typical)
Over Range Protection : 2X Rated Pressure
Burst Pressure : 5X or 20,000 PSI whichever is less
Pressure Cycles : >100 Million
Environmental Data
  Temperature  
Media : -55 to 125°C (-67 to 257°F)
Operating (Ambient) : -10°C to 70°C (14°F to 158°F)
Storage : -10°C to 85°C (14°F to 185°F)
  Thermal Limits  
Compensated Range : 0°C to 55°C (32°F to 131°F)
TC Zero : <±1.5% of FS
TC Span : <±1.5% of FS
Download Data Sheet
Request A Quote